Michigan
State University Extension
Home Maintenance And Repair
06/24/03
Maintaining Conventional Residential Oil-Fired Heating Systems
Greg Tuttle, Graduate
Student, Department of Agricultural Engineering
Susan Mireley, Associate Professor and Extension Housing Specialist
Department of Human Environment and Design
This publication covers maintenance of conventional oil-fired heating
systems only Information on maintenance and repair of the newer oil
furnaces is not covered.
Periodically, oil-fired heating systems need adjustment to keep them
running in the safest, most efficient and least costly manner. This
publication is designed to help you understand how oil-fired heating
systems work (both forced air and hot water systems), what periodic
preventive maintenance tasks the units should have, and what special
tasks and problems might arise that would need the attention of a
heating contractor.
All oil-fired heating systems are composed of a heat producing source
(a furnace in the case of forced air systems and a boiler for hot water
systems) heat exchanger; a distribution system (ducts in the case of
forced air systems, pipes in hot water systems); a burner by-products
elimination system (exhaust stack, flue or chimney); and control
mechanisms (such as the thermostat and master switch). Understanding
how these various parts operate and work together is an important part
of any preventive maintenance program.
Figure 1.
HOW AN OIL-FIRED HEATING SYSTEM WORKS
How the Typical Oil Burner Works
When a room thermostat is turned up or the room temperature drops below
the thermostat setting, the unit signals the furnace or boiler that
additional heat is needed. As a result of the signal, the burner motor
activates the fuel oil pump, sending fuel oil to a nozzle at the end of
an air tube (see Figs.
1 and
2). Under high pressure, the fuel oil is pushed through the nozzle
to form a fine mist. At the same time, the burner blower, also operated
by the burner motor, blows room air into the same air tube. The two-the
air and the fuel oil mist-combine to form a highly flammable vapor that
is then ignited by a spark supplied by the ignition electrodes. Once
started, the flames continue to burn in the combustion chamber with
additional fuel oil and room air supplied through the air tube/ nozzle.
In turn, the combustion gases from the flame flow through the flue
passageways of the heat exchanger, heating it, and then continue to
flow up and out the exhaust stack (see Fig.
1 for a forced air distribution system and Fig.
2 for a hot water distribution system). In the meantime, heat is
transferred from the flue gases through the heat exchanger walls to the
heat distribution medium (either air or water) that flows through the
supply system, distributing heat to various parts of the home.
How a Typical Forced Air Distribution
System Works
When the air temperature in the heat exchanger reaches a predetermined
temperature, which is controlled by a fan-and-limit control, the
furnace blower begins pulling cool room air through the return air
registers and ducts (see Figs.
1 and
3). The air is passed through a filter to clean it of dust.
It then passes through the heat exchanger, as described above, where it
is warmed by the hot combustion gases passing through the heat
exchanger on their way out of the house. The furnace blower then forces
the warm supply air into a plenum and through the supply ducts, finally
distributing it through supply registers in each room in the home. The
two air supplies, the combustion air and the air distributed through
the house system, should never come in direct contact with each other.
How a Hot Water Distribution System
Works
When a house thermostat calls for heat from a hot water distribution
system, the circulator pump is activated (see Fig.
2) and supplies hot water held in reserve in the boiler throughout
the distribution system-through the supply main, the supply branches
During the heating season, furnaces and boilers can accumulate a
build-up of dirt. In addition, the various moving parts wear. Dirt and
wear can lead to a loss of system efficiency, system failures, and
health and safety problems. Annual inspections and maintenance are
required to keep an oil-fired and finally the baseboard units (i.e.,
radiators or convectors in some systems) in the various rooms (see Fig.
4). As cool room air passes over the warmed baseboard unit
surfaces, the air absorbs heat and distributes it throughout the room.
Individuals, furnishings and objects near the baseboard units are also
warmed by heat given off by the units. The now cool water completes the
cycle, flowing from the baseboard units through the return branches and
the return main back to the boiler.
When the water in the boiler drops below a predetermined temperature,
the aquastat activates the burner (see Fig.
2). The heat given off by the burner warms the heat exchanger and
rewarms the water in the boiler, which holds it in reserve until the
circulator pump moves the water through the distribution system once
again. This two-phase process enables the system to maintain an on
demand supply of hot water at all times. The homeowner does not have to
wait for the water to be reheated and circulated through the system.
MAINTENANCE AND INSPECTION YOU CAN DO
During the heating season, furnaces and boilers can accumulate a
build-up of dirt. In addition, the various moving parts wear. Dirt and
wear can lead to a loss of system efficiency, system failures, and
health and safety problems. Annual inspections and maintenance are
required to keep an oil-fired heating system operating efficiently and
safely. You can do a number of the maintenance and inspection tasks
yourself. You may want to ask your heating contractor to show you some
of the procedures during his or her next visit or consult your heating
system owner’s manual. It should provide an excellent guide to
the types of activities do-it-yourselfers can do. This
publication describes some of those activities in a general way, but
the owner's manual will give you specifics for your system. If the
owner's manual is not available, write to the manufacturer and request
that one be sent to you. You will find the manufacturer’s name and
probably the address on the nameplate affixed to your unit somewhere.
If the manufacturer's address is not available, consult your heating
contractor or search the Yellow Pages to find the name of a heating
contractor that sells the brand you own. In your letter, give the model
and serial number of your unit so the correct owner's manual can be
sent to you. Both numbers can be found on the unit's nameplate If you
are a novice do-it yourselfer, follow the manufacturer's
recommendations carefully, and do only those tasks explained in the
manual. All others should be done by a heating contractor.
Figure 2.
Oil
is an efficient and safe fuel if the equipment burning it
is well maintained by knowledgeable people. Novices and inexperienced
tinkerers should be aware of the potential for creating problems.
The Furnace/Boiler
1. Change the fuel oil filter periodically (see Figs.
1 and
5). The fuel filter cleans the fuel of any impurities (e.g., dirt
and water) that may affect the efficient supply, ignition and burning
of the fuel. Consult the owner's manual for the correct procedure.
2. Clean and lubricate the burner motor (see Fig.
1). Dust and oil buildup will shorten the life of the burner motor.
Vacuum away any loose dust and wipe away any oil buildup or greasy
dirt. Lubricate the burner motor according to your owner's manual.
3. Inspect the burner mounting plate for evidence of leaks (see Fig.
1). They can alter the fuel/air mixture and allow smoke to escape
into the room. If smudges are present around the plate, call your
heating contractor to correct the situation.
4. Inspect the furnace's/ boiler's electrical system (i.e., master
switch and electrical cable, see Fig.
1). Electrical problems affect the performance of a unit and also
present a safety hazard. Bad connections, bare wires, blown
fuses, tripped circuit breakers and tripped reset buttons (the reset
button automatically disconnects the electricity to an overloaded
electrical motor) indicate that an electrical problem is present.
Contact your heating C-6ntractor to correct it. (Warning: electricity
is potentially dangerous for people not familiar with its operation.
Repairs should be made by a qualified service person.)
5. Inspect the exhaust stack for bad connections and damaged or
corroded pipes (see Figs.
1 and
2). Replace if damage is evident.
Figure 3.
6. Clean the draft regulator, the mechanism controlling the rate at
which combustion gases are pulled up and out the exhaust stack (see Figs.
1 and
2). Soot and dust buildup can interfere with the draft regulator's
efficient operation. Vacuum any loose dust and wipe off any greasy
soot. Also clean the back side of the hinged plate. Any modifications
or changes in the draft regulator setting should be done by a qualified
service person.
7. Inspect the fuel storage tank for leaks. Clues include oil stains or
puddles and/or a strong odor in the vicinity of the tank. Call a
heating contractor to replace the unit.
8. Clean the furnace room periodically. Dirt and lint from areas
surrounding the unit can be pulled into the burner along with
combustion air. Eventually they will slow the movement of combustion
air to the unit, causing it to burn inefficiently and give off soot.
9. Clean and adjust the room thermostats. Dust buildup interferes with
efficient thermostat operation. Remove the cover and wipe away dust
with a soft brush, such as a watercolor paint brush. Work carefully-
thermostats are fragile.
10. Observe the color of smoke leaving the chimney. Black smoke is a
sign of poor combustion. Call a heating contractor to make needed
adjustments.
11. Inspect any visible sections of the chimney and the chimney top. If
they are worn or damaged, consult your heating contractor.
12. Most oil furnaces are equipped with a reset button located on
either the stack control or the primary control-the safety devices that
shut the burner off if a flameless condition exists. Stack controls are
found on older units, while primary controls are found on newer ones.
If the reset button trips the burner off, a fuel supply or
ignition problem has occurred. Push the reset button once to restart
the burner. If the reset button trips the burner off again, contact
your heating contractor.
13. Safety note: oil-fired furnaces and boilers require an adequate
supply of air to ensure proper and safe burning of the fuel. In
addition, adequate clearances are necessary between combustibles such
as walls, doors and framing members and the furnace/boiler, the vent
stack and the chimney Never enclose a unit unless you check with a
heating contractor about the unit's combustion air needs. Never store
combustible materials near the unit.
Forced Air Distribution System
1. Clean the blower fan and the blower housing and clean and lubricate
the blower fan shaft and the blower motor (see Fig.
1). Dust, dirt and debris buildup affects the efficient operation
and useful life of these components. Remove it with a vacuum or soft
cloth and lubricate according to your owner's manual. (Note: some newer
units may not require lubrication because the bearings are sealed.)
Warning: shut off electricity to the unit before starting these
procedures.
2. Inspect the blower fan belt for wear and correct tension (see Fig.
1). It is fairly common for the belt to be too tight, which can
lead to premature failure of the motor or fan bearings and possible
belt breakage. On the other hand, a loose belt can slip, causing faster
belt wear and premature belt failure. Replace the belt when slippage
can no longer be corrected or belt failure seems likely. Adjust the
belt tension according to your furnace's owner's manual. (Note: many
newer oil furnaces do not have a fan belt-a motor drives the fan
directly.) Warning: shut off electricity to the unit before starting
belt adjustment.
3. Replace the air filter periodically to ensure that air is
circulating freely and cleanly (see Fig.
1). Dirty air filters slow air movement, make other furnace
components work harder (which shortens their useful life), and waste
energy. Inspect them monthly initially to determine how often they
should be changed. Follow directions provided in the furnace owner's
manual.
4. Inspect duct work for air leaks that result in heat loss and wasted
money (see Fig.
3). While the fan is operating, locate them by running your hand
over areas where you suspect leaks. Seal leaks with duct tape.
5. Clean and clear the room supply and return air registers of any dust
or obstructions (see Fig.
3). They reduce air circulation and waste energy dollars. A vacuum
will do a good job.
6. Any warning signs noted during the heating season such as unusual
odors from the registers, discoloration over registers, excessive dirt
in the house air supply, or unusual cycling of the burner or fan or
both should be reported to your heating contractor.
7. Periodically throughout the heating season, make a conscious effort
to listen to your unit as it goes through a heating cycle. The normal
procedure is: the room thermostat calls for heat, the burner goes on,
the fan then starts. Both should remain on until the thermostat
temperature is satisfied. Once it is satisfied, the burner stops first,
followed by the fan. If the burner or the fan or both cycle on and off
frequently before the thermostat is satisfied, a problem exists.
Consult your heating contractor. Likewise, if the burner ever goes on
but the fan does not follow, call a heating contractor.
Hot Water Distribution System
1. Clean the circulator motor and lubricate the motor and circulator
pump (see Fig.
2). Dust and dirt buildup inhibit efficient operation. Consult your
owner's manual for instructions and lubrication needs.
2. Clean and bleed baseboard units (convectors or radiators in some
systems; see Fig.
4). Both dust and dirt buildup on the baseboard unit's fins and air
in the pipes decrease the heat transfer efficiency of the baseboard
unit. A vacuum and a softbristle brush work well together for cleaning
the fins. If air is present in the pipes, you'll hear a sound similar
to water trickling. Bleed the unit by opening the air valve until water
runs freely from the unit. Then close the valve. (Note: many modern hot
water systems contain automatic bleeders and do not require this step.
Consult and follow your owner's manual for the correct procedures.)
3. Inspect baseboard units to ensure that adequate clearance exists
between them and the floor, particularly carpeted floors. Clearance is
necessary to allow air to flow freely around the unit. If your hand
cannot slip easily into this area, consult a heating contractor about
raising the unit.
Figure 4.
MAINTENANCE AND INSPECTION A SERVICE
PERSON SHOULD DO
Though you can do the maintenance and repair tasks described in your
owner's manual, other jobs require the knowledge of a heating
contractor. Inexperienced homeowners attempting these tasks may make
mistakes that expose them and their families to unnecessary hazards and
possibly damage the equipment. We mention these tasks because a heating
contractor should do them during a regular maintenance visit. When
selecting a contractor, ask about the standard service procedures
followed and see if they are similar to those described here. We
suggest that a heating contractor service your system every year. The
cost will be approximately $50 per visit.
Figure 5.
The Furnace/Boiler
1. Clean or replace the burner nozzle (see Fig.
1). With use, the burner nozzle passage ways may become partially
blocked or enlarged. In either case, the amount of fuel oil being
delivered to the combustion chamber will not be correct and the
resulting fuel/air mixture will contain either too much or too little
fuel. Both conditions will lower the efficiency of the furnace or
boiler.
2. Clean the burner blower (see Fig.
1). Dirt buildup on the blower causes an improper air/oil mixture
by cutting down on the amount of air supplied to the unit and lowers
the efficiency of the burner.
3. Adjust the burner flame (see Figs.
1 and
2). An improper burner flame level will generate less heat per unit
of fuel than the proper flame could produce.
4. Inspect, clean and adjust the ignition electrodes (see Fig.
1). If ignition does not occur because of a problem with the
electrodes and the fuel/air mixture continues to be pumped into the
combustion chamber, an explosive condition will exist, an obvious
safety hazard.
5. Inspect and clean the transformer (see Figs.
1 and
2). The transformer amplifies the electrical voltage supply (from
110 to 120 volts to 5,000 to 10,000 volts) to the electrodes,
initiating the spark that starts combustion.
6. Adjust the air volume control (see Figs.
1 and
2). This mechanism controls the amount of air in the
fuel/air mixture, a major factor affecting burner efficiency.
7. Inspect and adjust the fuel oil pump, which regulates the amount and
the pressure of fuel oil in the fuel/air mixture (see Figs.
1 and
2) Improper calibration of the fuel oil pump decreases furnace or
boiler efficiency.
8. Inspect, adjust and clean stack control, a necessary safety device
(see Figs.
1 and
2). If the furnace or boiler is operating in a flameless condition,
the stack control will shut down the burner. It needs to be functioning
well at all times. (Newer units do not have a stack control. They have,
instead, a solid state primary control, which incorporates a cad cell,
a lightsensitive mechanism that monitors electricity to the burner,
shutting the burner down if a flame is not produced. The cad cell
should be inspected for dirt and soot accumulation and cleaned as
needed. It should also be realligned.)
9. Adjust the draft regulator (see Figs.
1 and
2). Improper adjustment can result in excessive heat loss up the
flue.
10. Clean the heat exchanger surfaces (see Figs.
1 and
2). Cleaning improves heat transfer between the heat exchanger and
the heating medium (the air or water supply).
11. Check for combustion leaks. Combustion leaks allow dangerous gases
to escape into the furnace room.
12. Perform efficiency tests and make required adjustments. Efficiency
tests help the contractor determine burner efficiency and overall
furnace or boiler efficiency and point to specific areas where
adjustments can be made to increase efficiency. These tests are
essential to ensure that your oil furnace or boiler is running at its
peak level of performance. Because of their importance, the tests are
described and explained in more detail on pages 14-15.
Figure
6.
Forced Air Distribution System
1. Align the blower pulley and the blower motor (see Fig.
1). Improper alignment can cause abnormal belt wear and slippage.
(Note: most newer oil furnaces do not have pulleys a motor drives the
fan directly.)
2. Adjust the blower fan speed (see Fig.
1). Excessive fan speed will cause duct noise and waste
electricity. If the fan is set unnecessarily low, an excessive amount
of heat will be lost through the supply ducts before it reaches the
registers to provide room heat.
3. Adjust and test the fan-and limit control, which measures the
temperature of the air surrounding the heat exchanger. It automatically
turns the furnace blower on and off during each burning cycle and shuts
the burner down if the heat exchanger becomes overly hot. The control
monitors three temperatures: a fan-on temperature, a fan-off
temperature and a temperature limit, which is a safety device designed
to shut the burner off if the heat exchanger becomes too hot. It is
never adjusted or changed-the other two can be, however, For example,
the fan-on temperature is usually about 135 degrees F. When the air
around the heat exchanger reaches this temperature, the blower fan
comes on and moves the heated air throughout the home. The fan-off
temperature is usually set at approximately 100 degrees F. When the air
surrounding the heat exchanger reaches this temperature, the fan blower
stops so it doesn't circulate cool air through the home and cause
uncomfortable drafts. To save energy, you may want to ask your heating
contractor to lower these two temperature settings to a level closer to
the house thermostat setting. As a result, the furnace will supply more
heat to the house BUT the air will feel cooler. You may experience some
draftiness and discomfort after the changes until you become accustomed
to the new settings.
Hot Water Distribution System
1. Check the circulator pump coupler for wear and broken coupler
springs (see Fig.
2). The coupler connects the motor with the pump. Normally, if the
coupler springs are broken, a loud racket occurs; they have been known
to be broken, however, with little noise.
2. Check the operation of all safety controls (see Fig.
2), such as the safety relief valve, which would relieve the system
if overly high pressure should occur because of overheating.
3. Check and adjust air and water levels in the expansion tank, which
provides a reservoir for the safe collection of water as it expands
during the heating cycle (see Fig.
2). Note: many new expansion tanks contain bladder or diaphragm
devices that control water and air levels automatically.
Potential Problems
and Causes
Potential Problems
and Causes part 2
OIL FURNACE OR BOILER EFFICIENCY TESTS
Efficiency tests are the best means available to determine if your oil
furnace or boiler is functioning at its maximum efficiency level and
thus providing you with the most heating output for your energy
dollars. Efficiency tests indicate the amount of heat output you are
receiving in relation to fuel input into the system.
Efficiency tests should be done by a heating contractor because
performing them and making necessary adjustments requires specialized
knowledge. In addition, the equipment needed to perform them is
specialized and relatively expensive. Four tests should be conducted to
ensure that a furnace achieves maximum efficiency.
Efficiency tests are a series of flue gas measurements: a draft volume
measurement, a smoke test, a carbon dioxide (C02) percentage reading
and a flue gas temperature reading. The first two tests are done to
make burner adjustments, and the others provide a measure of the
overall efficiency of the system. The equipment required for these
tests includes a draft gauge, a smoke tester, C02 indicator and a flue
gas thermometer.
Two steps have to be taken before conducting the tests. First, a hole
must be drilled in the flue pipe close to the body of the
furnace/boiler and ahead of the draft regulator. This hole will be used
to insert the test equipment and provide readings. After the tests are
completed, it can be replugged with a sheet metal screw. Second,
immediately before testing, the furnace or boiler must be brought up to
its normal operating temperature. This can be accomplished by turning
the house thermostat above its normal reading for 10 to 15 minutes. The
tests are then conducted.
The first test conducted measures the amount of draft or the speed of
the movement of combustion gases up the chimney. The test indicates how
forcefully the gases are being moved out of the house. The test probe
of the draft gauge is inserted into the flue pipe hole and the reading
recorded. A high draft reading indicates that the hot gases are being
drawn up the flue too quickly and excessive heat is being wasted
through the chimney. A low draft reading, on the other hand, indicates
the gases are not being vented quickly enough. To correct draft
problems, the heating contractor will adjust air intake to the burner
and combustion chamber and the balance weight on the draft regulator
door.
Figure 7.
The second test is a smoke test, which indicates the soot content of
the flue gases. The probe for the smoke tester is inserted into the
flue pipe hole and a specified amount of smoke is drawn through filter
paper. The darkened filter paper is then compared to a smoke test scale
(ranging from 0 to 10) supplied with the test kit. Anything higher than
2 on the scale means the air/fuel mix is poor and an excessive amount
of unburned fuel is escaping up the chimney. The heating contractor
will adjust the air supply to the burner to achieve a more smokeless
flame.
Measuring and adjusting the furnace or boiler's draft and achieving a
low smoke test number set the stage for accurate C02 and stack
temperature tests. These final two tests are used to calculate the
operating efficiency of the unit.
The contractor measures the C02 content of the flue gas to determine if
excess air is present in the flue. It is accomplished by inserting the
C02 indicator probe into the flue pipe hole and extracting a specified
amount of flue gas. The reading should register somewhere between 0 and
14 percent. If the percentage of C02 is low (less than 8 percent, for
example), the air/fuel mix is high in excess air, and valuable heat is
being wasted out the flue or chimney. The heating contractor should
adjust the air/fuel mixture.
Finally, the flue gas temperature is taken to determine the unit's
ability to utilize heat and not waste it. It is measured by inserting
the flue gas thermometer into the flue pipe hole. A high flue gas
temperature, such as 500 to 550 degrees F or over, indicates an
excessive amount of heat is escaping up the chimney, thus wasting
energy dollars. Low temperatures, on the other hand, such as 300 to 350
degrees F. or lower, indicate that corrosive condensation may be
occurring in the chimney. The contractor will correct either situation.
The results of the C02 and flue gas temperature tests are applied to a
chart similar to the one shown in Fig.
7, which provides an indication
of furnace or boiler efficiency. The C02 percentage reading is located
along the horizontal line of the graph and the flue gas temperature is
located along the vertical line. The point inside the graph where lines
from these plotted points intersect indicates furnace efficiency. An
efficiency percentage below 75 percent indicates that the flue gas
temperature is too high and the percent C02 in the flue gas is too low.
We strongly urge that you have a heating contractor perform the
efficiency tests annually. The cost of hiring a contractor varies, but
on the average, it runs approximately $50 for a regular maintenance
visit. The contractor should be able to estimate the time needed and
thus the additional cost for conducting the tests. The potential
savings on your annual heating bill from the adjustments could very
well pay for the call and perhaps save some extra dollars as well.
References
Maintaining
Conventional Residential Gas-Fired Heating Systems, Michigan
State
University
Extension E2110
Brotherson, Donald. ''Heating the Home,'' G3.1. Small Homes
Council-Building Research Council, University of Illinois, 1976.
Energy, Mines and Resources Canada. "The Billpayer's Guide to Heating
Systems.'' Minister of Supply and Services, Canada, 1983.
Knight, Paul A. Mechanical Systems Retrofit Manual.- A Guide for
Residential Design. New York: VanNostrand Reinhold Company, 1987.
Mireley, Susan and Don D. Jones. "The Indiana Do It Yourself Home
Maintenance Checklists: Space Conditioning Systems," HE-
63. Indiana Cooperative Extension Service, Purdue University, July 1986.
Other references

Other references part 2

Return
to main page
This information is for
educational purposes only. References to commercial products or trade
names does not imply endorsement by MSU Extension or bias against those
not mentioned. This information becomes public property upon
publication and may be printed verbatim with credit to MSU Extension.
Reprinting cannot be used to endorse or advertise a commercial product
or company.
MSU is an
affirmative-action, equal-opportunity
employer. Michigan State University Extension programs and materials
are open to all without regard to race, color, national origin, gender,
gender identity, religion, age, height, weight, disability, political
beliefs, sexual orientation, marital status, family status or veteran
status. Issued in furtherance of MSU Extension work, acts of May 8 and
June 30, 1914, in cooperation with the U.S. Department of Agriculture.
Thomas G. Coon, Director, MSU Extension, East Lansing,MI 48824. This
information is for educational purposes only. Reference to commercial
products or trade names does not imply endorsement by MSU Extension or
bias against those not mentioned.
This
information.was reviewed as
of June 2008. For more information about the contents please
contact costner@msu.edu
for webpage problems
strausc@msu.edu .